adjust docs for #1918
Less noise requires slightly modified parameters for the heating system.
This commit is contained in:
@@ -212,10 +212,10 @@ The NSPanel works nicely as a replacement for existing water underfloor heating
|
||||
In my specific use case, the control valve is of the 'normally closed' type, meaning that an open relay indicates 'no heating.'
|
||||
I have utilized relay #1 for this purpose. It's important to note that this setup does not act as a PID controller but operates on a simple on-off mechanism.
|
||||
The system initiates heating at a preset value below and turns it off at a value above the set point.
|
||||
I have set these values to `0.3°C` below and `0.1°C` above the target temperature, respectively.
|
||||
These adjustments, `0.3` and `0.1`, have been effectively maintaining the desired temperature in all of our four rooms.
|
||||
I have set these values to `0.1°C` below and `0.1°C` above the target temperature, respectively.
|
||||
These adjustments have been effectively maintaining the desired temperature in all of our four rooms.
|
||||
The thermostat's settings range from a minimum of `15°C` to a maximum of `22°C`, with a granularity of `0.1°C` for adjustments.
|
||||
Furthermore, I have selected `21.2°C` as the default target temperature.
|
||||
Furthermore, I have selected `18.3°C` as the default target temperature.
|
||||
|
||||
```yaml
|
||||
##### addon-configuration #####
|
||||
@@ -224,21 +224,23 @@ Furthermore, I have selected `21.2°C` as the default target temperature.
|
||||
temp_min: "15"
|
||||
temp_max: "22"
|
||||
temp_step: "0.1"
|
||||
cold_tolerance: "0.3"
|
||||
cold_tolerance: "0.1"
|
||||
hot_tolerance: "0.1"
|
||||
|
||||
##### CHANGE ME END #####
|
||||
climate:
|
||||
- id: !extend thermostat_embedded
|
||||
visual:
|
||||
temperature_step: ${temp_step}
|
||||
preset:
|
||||
- name: Home
|
||||
default_target_temperature_low: 21.2
|
||||
default_target_temperature_low: 18.3
|
||||
mode: "heat"
|
||||
```
|
||||
|
||||
Please note that employing any filter to smooth the temperature readings, such as averaging, is discouraged.
|
||||
Please note that employing any filter to smooth the temperature readings, such as averaging, is discouraged if the relevant timescale exceeds 1min.
|
||||
Such filtering methods can delay the response times of an already slow underfloor heating system.
|
||||
Despite this, the temperature stability achieved is quite satisfactory, as illustrated in the graph below.
|
||||
|
||||

|
||||
*On March 5th, around 9:30 PM, a window was opened, and all heaters were set to 'off.'*
|
||||
*On March 24th (around 9:20 PM) and March 25th (around 7:30AM) a window was opened, and all heaters were set to 'off.' for 30min*
|
||||
|
||||